Code No | SH1225 | SH2425 | SH3625 | SH1225F | SH2425F | SH3625F | SH1263 | SH2463 | SH3663 | SH1263F | SH2463F | SH3463F |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Bushing Type (HV) | 10NI250 | 20NI250 | 30NI250 | 10NF250 | 20NF250 | 30NF250 | 10NI630 | 20NI630 | 30NI630 | 10NF630 | 20NF630 | 30NF630 |
Specification (DIN) | 42531 | 42531 | 42531 | 42531 | 42531 | 42531 | 42531 | 42531 | 42531 | 42531 | 42531 | 42531 |
Nominal Voltage (kV) | 10 | 20 | 30 | 10 | 20 | 30 | 10 | 20 | 30 | 10 | 20 | 30 |
Rated Current | 250 | 250 | 250 | 250 | 250 | 250 | 630 | 630 | 630 | 630 | 630 | 630 |
Maximal Voltage (kV) | 12 | 24 | 36 | 12 | 24 | 36 | 12 | 24 | 36 | 12 | 24 | 36 |
Dry Lightning Impulse Voltage | 75 | 125 | 170 | 75 | 125 | 170 | 75 | 125 | 170 | 75 | 125 | 170 |
Wet power frequency Volt (kV) | - | - | - | 28 | 50 | 70 | - | - | - | 28 | 50 | 70 |
Drypower frequency Volt (kV) | 28 | 50 | 70 | -v | - | - | 28 | 50 | 70 | - | - | - |
Creepage Distance (mm) | 170 | 295 | 445 | 295 | 445 | 635 | 170 | 295 | 445 | 295 | 445 | 635 |
Arching Distance (mm) | 85 | 155 | 220 | 85 | 155 | 220 | 85 | 155 | 220 | 85 | 155 | 220 |
Electrical Properties Of HV Bushings | ||||||||
---|---|---|---|---|---|---|---|---|
Type | Norm | Nominal Voltage (kV) | Rated Current (A) | Dry Lightening Impulse Voltage (kV) | Wet Power Frequency Voltage (kV) | Dry Power Frequency Voltage (kV) | Creepage Distance (mm) | Total Weight (kg) |
10 NI 250 | DIN 42531 | 12 | 250 | 75 | - | 28 | 170 | 3.1 |
10 NF 250 | DIN 42531 | 12 | 250 | 75 | 28 | - | 290 | 4.2 |
20 NI 250 | DIN 42531 | 24 | 250 | 125 | - | 50 | 290 | 4.2 |
20 NF 250 | DIN 42531 | 24 | 250 | 125 | 50 | - | 440 | 5.4 |
30 NI 250 | DIN 42531 | 36 | 250 | 170 | - | 70 | 440 | 5.4 |
30 NF 250 | DIN 42531 | 36 | 250 | 170 | 70 | - | 580 | 6.4 |
10 NI 630 | DIN 42532 | 12 | 630 | 75 | - | 28 | 170 | 4.8 |
10 NF 630 | DIN 42532 | 12 | 630 | 75 | 28 | - | 290 | 5.3 |
20 NI 630 | DIN 42532 | 24 | 630 | 125 | - | 50 | 170 | 5.3 |
20 NF 630 | DIN 42532 | 24 | 630 | 125 | 50 | - | 440 | 7.9 |
30 NI 630 | DIN 42532 | 36 | 630 | 170 | - | 70 | 440 | 7.9 |
30 NF 630 | DIN 42532 | 36 | 630 | 170 | 70 | - | 630 | 9.9 |
20 NF 1000 | DIN 42533 | 24 | 1000 | 125 | 50 | - | 435 | 18.6 |
30 NF 1000 | DIN 42533 | 36 | 1000 | 170 | 70 | - | 635 | 22.3 |
10 NF 2000 | DIN 42533 | 12 | 2000 | 75 | 28 | - | 290 | 25.3 |
20 NF 2000 | DIN 42533 | 24 | 2000 | 125 | 50 | - | 440 | 29.4 |
30 NF 2000 | DIN 42533 | 36 | 2000 | 170 | 70 | - | 665 | 35.1 |
10 NF 3150 | DIN 42533 | 12 | 3150 | 75 | 28 | - | 290 | 28.9 |
20 NF 3150 | DIN 42533 | 24 | 3150 | 125 | 50 | - | 435 | 33 |
30 NF 3150 | DIN 42533 | 36 | 3150 | 170 | 70 | - | 665 | 39.2 |
45 NF 1000 | DIN 42534 | 52 | 1000 | 250 | 95 | - | 1090 | 35.2 |
Mechanical Properties Of HV Bushings | ||||||||
---|---|---|---|---|---|---|---|---|
Type | Specification (DIN) | Operation Bending Load ACC. To IEC 137 (N) | Tightening Torque(Nm) | |||||
10 NI 250 | DIN 42531 | 2500 | 20 | |||||
10 NF 250 | DIN 42531 | 600 | 20 | |||||
20 NI 250 | DIN 42531 | 600 | 20 | |||||
20 NF 250 | DIN 42531 | 600 | 20 | |||||
30 NI 250 | DIN 42531 | 600 | 20 | |||||
30 NF 250 | DIN 42531 | 600 | 20 | |||||
10 NI 630 | DIN 42532 | 1300 | 35 | |||||
10 NF 630 | DIN 42532 | 1300 | 35 | |||||
20 NI 630 | DIN 42532 | 1300 | 35 | |||||
20 NF 630 | DIN 42532 | 1300 | 35 | |||||
30 NI 630 | DIN 42532 | 1300 | 35 | |||||
30 NF 630 | DIN 42532 | 1300 | 35 | |||||
10 NF 1000 | DIN 42533 | 1700 | 70 | |||||
20 NF 1000 | DIN 42533 | 1700 | 70 | |||||
30 NF 1000 | DIN 42533 | 1700 | 70 | |||||
10 NF 2000 | DIN 42533 | 2900 | 100 | |||||
20 NF 2000 | DIN 42533 | 2600 | 100 | |||||
30 NF 2000 | DIN 42533 | 2200 | 100 | |||||
10 NF 3150 | DIN 42533 | 3200 | 200 | |||||
20 NF 3150 | DIN 42533 | 2800 | 200 | |||||
30 NF 3150 | DIN 42533 | 2200 | 200 | |||||
45 NF 1000 | DIN 42534 | 1600 | 250 |